ABB TTR200 Operating	 Instruction Download Page 8

   

8  OI/TTR200-EN Rev. B | 

TTR200 

3

 

Use in potentially explosive 
atmospheres in accordance with FM 
and CSA 

 

NOTICE

 

 

—  Further information on the approval of devices for use in 

potentially explosive atmospheres can be found in the 
explosion protection test certificates (at 
www.abb.com/temperature). 

—  Depending on the design, a specific marking in 

accordance with FM or CSA applies. 

 

3.1

 

Ex-marking 

FM Intrinsically Safe 

 

Model TTR200-L6 

Control Drawing 

TTR200-L6H (I.S.) 

Class I, Div. 1 + 2, Groups A, B, C, D 

Class I, Zone 0, AEx ia IIC T6 

 

FM Non-Incendive 

 

Model TTR200-L6 

Control Drawing 

TTR200-L6H (N.I.) 

Class I, Div. 2, Groups A, B, C, D 

 

CSA Intrinsically Safe 

 

Model TTR200-R6 

Control Drawing 

TTR200-R6H (I.S.) 

Class I, Div. 1 + 2, Groups A, B, C, D 

Class I, Zone 0, Ex ia Group IIC T6 

 

CSA Non-Incendive 

 

Model TTR200-R6 

Control Drawing 

TTR200-R6H (N.I.) 

Class I, Div. 2, Groups A, B, C, D 

 

 

 

3.2

 

Installation instructions 

3.2.1

 

FM / CSA 

The installation, commissioning, maintenance and repair of 
devices in areas with explosion hazard must only be carried 
out by appropriately trained personnel. 
The operator must strictly observe the applicable national 
regulations with regard to installation, function tests, repairs, 
and maintenance of electrical devices. (e.g. NEC, CEC). 
 

3.2.2

 

IP protection rating of housing 

The temperature transmitter must be installed such that the IP 
rating of at least IP 20 is achieved in accordance with 
IEC 60529. 
 

3.2.3

 

Electrical connections 

Grounding 

If, for functional reasons, the intrinsically safe circuit needs to 
be grounded by means of a connection to the potential 
equalization, it may only be grounded at one point. 
 

Intrinsic safety proof 

If transmitters are operated in an intrinsically safe circuit, proof 
that the interconnection is intrinsically safe must be provided 
in accordance with IEC/EN 60079-14 as well as 
IEC/EN 60079-25.  
The supply isolators / DCS inputs must feature intrinsically 
safe input protection circuits in order to eliminate hazards 
(spark formation). 
In order to provide proof of intrinsic safety, the electrical limit 
value must be used as the basis for the EC-type examination 
certificates for the equipment (devices); this includes the 
capacitance and inductance values of the cables. 
Proof of intrinsic safety is said to have been provided if the 
following conditions are fulfilled when a comparison is carried 
out in relation to the limit values of the equipment: 

Summary of Contents for TTR200

Page 1: ...Operating Instruction OI TTR200 EN Rev B TTR200 Rail mount temperature transmitter Measurement made easy...

Page 2: ...on Additional documentation on TTR200 is available free of charge for downloading at www abb com temperature Alternatively scan this code Manufacturer ABB Automation Products GmbH Process Automation S...

Page 3: ...Storing the device 10 6 3 1 Ambient conditions 10 6 4 Returning devices 10 7 Installation 11 7 1 Installation 11 7 1 1 Installation on the rail 11 7 2 Electrical connections 11 7 2 1 Conductor materi...

Page 4: ...WARNING indicates an imminent danger Failure to observe this information may result in death or severe injury CAUTION The signal word CAUTION indicates an imminent danger Failure to observe this info...

Page 5: ...Da ib IIC T6 T1 Gb 2 2 Temperature data ATEX IECEx intrinsic safety Temperature class Permissible ambient temperature range Device category 1 use Device category 2 3 use T6 40 44 C 40 111 2 F 40 56 C...

Page 6: ...on In order to provide proof of intrinsic safety the electrical limit value must be used as the basis for the EC type examination certificates for the equipment devices this includes the capacitance a...

Page 7: ...ing II 3 G Ex nA IIC T1 T6 Gc Ex area Zone 2 Safe area Fig 5 A Sensor B Transmitter in the housing with IP rating IP 54 C Supply isolator When using the transmitter in Zone 2 observe the following The...

Page 8: ...plicable national regulations with regard to installation function tests repairs and maintenance of electrical devices e g NEC CEC 3 2 2 IP protection rating of housing The temperature transmitter mus...

Page 9: ...e may also be carried out in potentially explosive atmospheres using a handheld terminal that has been approved accordingly under consideration of an intrinsic safety installation check Alternatively...

Page 10: ...curred from improper transport Details of any damage that has occurred in transit must be recorded on the transport documents All claims for damages must be submitted to the shipper without delay and...

Page 11: ...om electrical circuits which are dangerous if touched or implement additional isolation measures for them Connections must only be established in a dead voltage state The transmitter has no switch off...

Page 12: ...ocouple I Terminal 11 Measurement of the 4 20 mA output current without opening interrupting the current loop J Without function 1 4 Sensor connection from measuring inset PWR green LED supply voltage...

Page 13: ...or short circuit and sensor wire breakage Linear resistance measurement Sensor wire break Input thermocouples voltages Types B E J K N R S T in accordance with IEC 60584 U L in accordance with DIN 437...

Page 14: ...gnal line When connecting the devices note the voltage drop on the signal line The minimum supply voltage on the transmitter must not be undershot Fig 11 A Transmitter B Supply isolator PCS input with...

Page 15: ...The advantage of this is that remote configuration is possible with supply units that are part of the industrial plant The following configuration types are available for the transmitter With the han...

Page 16: ...ue temperature Trim low using a water quench or oven It is important to make sure the temperature is balanced and stable In the DTM check that the proper adjustment temperature has been entered for th...

Page 17: ...system is corrected by the DA converter of the transmitter For the higher level system the value of the analog 4 20 mA output signal and the digital HART signal now match The adjustment should be rep...

Page 18: ...pe J IEC584 Thermocouple type N IEC584 Thermocouple type R IEC584 Thermocouple type S IEC584 Thermocouple type T IEC584 Thermocouple type L DIN43710 Thermocouple type U DIN43710 Thermovoltage 125 125m...

Page 19: ...ll address TAG Address Multidrop Specifies the communication type Address 0 conforms to HART operating mode point to point communication 4 20 mA output signal Address 1 15 conforms to HART multidrop o...

Page 20: ...sensor or unit fault is detected the red LED indirectly signals that the supply voltage is connected Once the sensor or unit fault is eliminated and the red LED turns off the supply voltage signal app...

Page 21: ...rective 2011 65 EC The products provided by ABB Automation Products GmbH do not fall within the current scope of regulations on hazardous substances with restricted uses or the directive on waste elec...

Page 22: ...s Contact person Telephone Fax E Mail Device details Typ Serial no Reason for the return description of the defect Was this device used in conjunction with substances which pose a threat or risk to he...

Page 23: ...Notes TTR200 OI TTR200 EN Rev B 23 Notes...

Page 24: ...perature Note We reserve the right to make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB does n...

Reviews: