3  Connections 

 

NB: The connection cable cross section area is 0.34 mm

2

 and cable length is 150 mm.

  

Caution! 

The connection cables should not be extended as longer cables increase the risk for electrical 

interference. 

 

Warning!

 

The information channel output shall 

never

 be used for the safety purpose(s). 

The connection cables are not monitored and must therefore be installed within the same physical enclosure as the 
safety device to maintain the highest safety level (fault exclusion, refer to EN ISO 13849-2:2003 Annex D). 

The safety adaptor shall 

not

 be used for purposes other than intended. All loading or tampering with the device can 

lead to serious risk of life.  

5-pole connection cables: 

1 )  Brown: 

+24 VDC 

2 )  White: 

Dynamic signal input 

3 )  Blue: 

0 VDC 

4 )  Black: 

Dynamic signal output 

5 )  Grey: 

Information 

Summary of Contents for Tina 2B

Page 1: ...ABB AB Jokab Safety Varlabergsv gen 11 SE 434 39 Kungsbacka Sweden www abb com lowvoltage Original instructions Tina 2A B Adaptor unit...

Page 2: ...FETY will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products This information by itself is not sufficient for a complete deter...

Page 3: ...iew 5 General description 5 Safety regulations 5 3 Connections 6 Connection examples 7 4 Installation and maintenance 8 Installation precautions 8 Maintenance 8 Testing of the safety functions 8 Troub...

Page 4: ...of this document has knowledge of the following Basic knowledge of ABB Jokab Safety products Knowledge of machine safety Special notes Pay attention to the following special notes in the document Warn...

Page 5: ...ty sensors without an M20 threaded connector The Tina2A B adaptor unit is intended for use in safety circuits in accordance with EN 60204 1 Warning In order to maintain the highest safety level and re...

Page 6: ...used for the safety purpose s The connection cables are not monitored and must therefore be installed within the same physical enclosure as the safety device to maintain the highest safety level faul...

Page 7: ...2TLC172121M0201 rev A 7 www abb com lowvoltage 2011 09 20 Connection examples Caution All cable colours according to ABB Jokab Safety standard cables...

Page 8: ...ions Make sure the safety unit is working properly by following these steps Interrupt the dynamic safety circuit before this unit The LED should flash between green and red Interrupt protection The LE...

Page 9: ...namic signal Dynamic signal input does not exist i e the safety circuit is interrupted before this unit 24 VDC A constant 24 VDC signal is applied high H 0 VDC The pin is connected to 0 VDC low L The...

Page 10: ...d 13 volt RMS Dynamic output between 9 and 13 volt RMS Information output 23 VDC General Protection class IP67 Ambient temperature Storage 30 70 C Operation 10 55 C Humidity range 35 to 85 with no ici...

Page 11: ...2TLC172121M0201 rev A 11 www abb com lowvoltage 2011 09 20 Dimensions Tina 2A Tina 2B NB All measurements in millimetres...

Page 12: ...to compile the technical file Lars Magnus Felth ABB AB JOKAB SAFETY Varlabergsv gen 11 SE 434 39 Kungsbacka Sweden Product Certificate Serialnumber Non contact safety sensor Eden Adam Eva E C EC 44 2...

Reviews: