Tel: (888) 552-6467
Fax: (800) 316-4515
www.tnb.com
06/18 750.1781_Rev. H
11/12
300/600W Mini Inverter
STATUS INDICATOR
(LED)
TROUBLESHOOTING GUIDE
DISPLAY
DETAIL
SYMPTOMS
PROBLEM
CORRECTIVE ACTION
LED Flashing
RED 1 times
every 6
seconds
Battery Failure Error
The battery did not last long
enough for a manual or monthly
test
Replace the batteries
The battery did not last long
enough for an annual test
Replace the batteries
Battery fail in charge
Replace the batteries
LED Flashing
RED 2 times
every 6
seconds
Charger Failure Error
Charger not working
Reset the unit (see page 4) and if the same error is
displayed, replace the charger board
LED Flashing
RED 3 times
every 6
seconds
Lamp Failure Error
Lost 10% or more if initial lamp
loading is lost
Replace the bad lamp and reset the unit
LED AMBER
(ORANGE)
steady On
Network server down
The Nexus modem is no longer
sending a signal to the Nexus
server.
See Nexus manual system
LED flashing
between
AMBER/OFF
Wink mode
The unit is in yellow blink mode
Stop the wink mode by sending a message from the
Nexus server or reset the unit (see page 4).
TROUBLESHOOTING GUIDE (PAGE 2 OF 2)