TERRA DC WALLBOX UL
2020-10-05
14/38
3.2.1
Required electrical grid configuration
It is essential that the Terra DC Wallbox 3-phase input variant is installed in the proper electrical grid
configuration. The allowable grid configuration is shown in the figure below.
Electrical grid configuration required for 3-phase, Terra DC Wallbox UL variant (3ø, 480Y/277V input)
3-phase
480Y/277V
Terra DC
Wallbox
Neutral
Grounding
Electrode
Conductor
277V
480V
Line 1
Line 2
Line 3
Neutral
Ground
Line 1
Line 2
Line 3
40A fused
switch or
circuit breaker