A5 = not applicable for socket version
•
A6 = authorization = RFID enabled
•
A7 = Ethernet = single
•
A8 = metering = not certified
•
A9 = SIM slot = applicable
•
A10 = display = not applicable
•
The '0' is an empty field.
11.2
Mass
EVSE type
Weight [kg]
Terra AC wallbox type 2 with socket (Eu-
rope)
2
Terra AC wallbox type 2 with an EV charge
cable (Europe)
3.5
Terra AC wallbox type 1 (North America)
4.5
11.3
Protective device compliance
11.3.1
Protective device compliance (Europe)
Requirements
Specifications
Dedicated upstream protection device(s)
Options:
•
RCD (Type A minimum) + MCB
•
RCBO (Type A minimum), (for exam-
ple: ABB model PN: DS201 C40 A30)
Upstream overcurrent protection breaker
(for example: RCBO or MCB).
Note: The breaker value de-
pends on the diameter and the
length of the cable, the EVSE
rating, and the environmental
parameters (for the electrician
to decide).
The breaker serves as the main disconnect
switch to the EVSE.
Breaker rating:
•
40A for a 32 Amp rated EVSE
•
20A for a 16 Amp rated EVSE
Upstream residual-current device (RCD)
Minimum Type A, with a rated residual op-
eration current of maximum 30 mA
Note: Internal to EVSE is DC
fault current monitoring > 6mA
Technical data
46