WBPEEUI210509A0
PR11 - 1
PR11
DC Bus Monitoring Assembly
Removal
Purpose/Scope
This procedure explains how to remove the DC bus monitoring
assembly from the rear of the power chassis.
Parts
None.
Tools
Bladed screwdriver.
Safety Considerations
Procedure
□
1. Be sure power is removed at the source before starting this
procedure.
□
2. Open the rear door of the cabinet.
□
3. Disconnect and label the cable from J1 (Fig.
PR11-1
) on
the DC bus monitoring assembly.
NOTE:
Do not disconnect or connect the cable from the DC bus monitoring
assembly to the DC bus bar while the system is operating. Doing so could
cause a PFI to occur.
□
4. Refer to Figure
PR11-1
and use the bladed screwdriver to
disengage the locking device on the DC bus monitoring
assembly.
□
5. Remove the DC bus monitoring assembly from the DIN
rail.
5 min.
WARNING
1. Disconnect power before attempting these procedures. Fail-
ure to do so could result in severe or fatal shock, or equipment
damage.
W1