36/78 SUREWAVE SFC USER MANUAL
––
8 Technical specifications
General product data
General
AC voltage
380 – 480 V line-line
AC frequency range
50 – 60 Hz
Efficiency
96% (typical @ 100% load)
THDi at the input terminals
< 3% (at rated load)
THDv at the output terminals
< 2.5% (linear load)
Overload capability
250% for 2 seconds
Graphic Display Module (GDM)
Functional, high res., resistive 10” display
Acoustic noise
< 80 dBA @ 1 m
Cooling exhaust
Top hat
Input termination cabinet (only > 750 kVA)
Left or right
Cable entry (only for > 750 kVA)
Top or bottom
Communication
MODBUS TCP/IP, Ethernet
Table 8-1: SureWave SFC technical specifications summary
––
250 kVA to 2.25 MVA range specifications
1 PE120
2 PE120
3 PE120
Module pairs (PEBBs)
1
2
3
4
5
6
7
8
9
Termination Cabinet
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
I/O Breaker
N/A
N/A
N/A
E4.2
2000
E4.2
2000
E4.2
2000
E4.2
3200
E4.2
3200
E4.2
3200
Breaker rating current [A]
N/A
N/A
N/A
2000
2000
2000
3200
3200
3200
Nominal output current [A]
300
600
900
1200
1500
1800
2100
2400
2700
Nominal output power [kVA]
250
500
750
1000
1250
1500
1750
2000
2250
Max output power [kW]
225
450
675
900
1125
1350
1575
1800
2025
Table 8-2: SureWave SFC complete range specifications