30/78 SUREWAVE SFC USER MANUAL
product type code represents a 2.25 MVA rated unit. Be aware that this rating can only be
achieved with input and output voltages at (480 Vac).
Output rating
Code
250 kVA
025
500 kVA
050
750 kVA
075
1000 kVA
100
1250 kVA
125
1500 kVA
150
1750 kVA
175
2000 kVA
200
2250 kVA
225
Table 7-1: SureWave SFC power rating type code
––
Input cable routing & CB
The SureWave SFC is available with provision for top or bottom cable routing for the input termi-
nation. Models between 250 kVA and 750 kVA only provides bottom cable routing.
Note, termination enclosures are only available for > 750 kVA models.
For protection reasons, it is necessary to supply the SFC through a suitably rated low voltage
circuit breaker. Models between 1 MVA and 2.25 MVA have circuit breaker installed by default
from the factory.