57/78 SUREWAVE SFC USER MANUAL
39
Uref Sat max
WARNING: Output Voltage ref-
erence exceeds the upper limit
threshold.
Check set point parameter is
within bounds
40
Uref Sat min
WARNING: Output Voltage ref-
erence set below the lower
limit threshold.
Check set point parameter is
within bounds
41
Freq ref Sat max
WARNING: Output Frequency
reference exceeds the upper
limit threshold.
Check set point parameter is
within bounds
42
Freq ref Sat min
WARNING: Output Frequency
reference set below the lower
limit threshold.
Check set point parameter is
within bounds
43
Vgen Q Sat max
WARNING: Virtual Generator Q
loop output has been limited
to Sat Max threshold.
AVR has wound up to its upper
limit. If in Fixed power, check
Qset set point maximum param-
eter is within bounds.
44
Vgen Q Sat min
WARNING: Virtual Generator Q
loop output has been limited
to Sat Min threshold.
AVR has wound down to its
lower limit. If in Fixed power,
check Qset set point minimum
parameter is within bounds.
45
Vgen P Sat max
WARNING: Virtual Generator P
loop output has been limited
to Sat Max threshold.
Governor has wound up to its
upper limit. If in Fixed power,
check Pset set point maximum
parameter is within bounds.
46
Vgen P Sat min
WARNING: Virtual Generator P
loop output has been limited
to Sat Min threshold.
Governor has wound down to its
lower limit. If in Fixed power,
check Pset set point minimum
parameter is within bounds.
47
Vgen Vlim Sat max
WARNING: Virtual Generator
output voltage has been lim-
ited to Sat Max threshold.
Voltage control has wound up to
its upper limit. If in Fixed power,
check Vlim set point maximum
parameter is within bounds.
48
Vgen Vlim Sat min
WARNING: Virtual Generator
output voltage has been lim-
ited to Sat Min threshold.
Voltage control has wound
down to its lower limit. If in
Fixed power, check Vlim set
point minimum parameter is
within bounds.
52
Thermal Overload
Warning
WARNING: Internal tempera-
ture has been measured as
higher than warning limit.
Check SFC fans and filters, and
repair / clean as necessary.
Check SFC load and reduce if
necessary. Check cooling fans,
filters, and repair / clean if nec-
essary.
Check ambient air temperature.
Check for cooling air recircula-
tion.
54
External Neg Se-
quence
WARNING: Negative Sequence
detected on External bus.
Check phase rotations of output
connections and Vsense meas-
urements
Table 10-5: SureWave SFC active events icons