2
SPCJ 4D40
Capacitor bank
protection relay module
Contents
Characteristics ................................................................................................................ 2
Description of function
(modified 97-10)
....................................................................... 3
Block diagram ................................................................................................................. 5
Front panel ..................................................................................................................... 6
Operation indicators ....................................................................................................... 7
Settings ........................................................................................................................... 8
Programming switches .................................................................................................... 9
Measured data............................................................................................................... 13
Recorded data ............................................................................................................... 14
Main menus and submenus of settings and registers ..................................................... 16
Time/current characteristics
(modified 99-10) ...............................................................
18
Technical data ............................................................................................................... 21
Event codes ................................................................................................................... 22
Data to be transferred over the bus ............................................................................... 23
Fault codes .................................................................................................................... 27
Characteristics
Two overload stages I
b
> and I
a
>. Stage I
b
>:
setting range 0.30...1.50 x I
n
, based on inverse
time characteristic, setting range 0.2...2.0 for
time multiplier k. Stage I
a
>: setting range
80...120 % I
b
, based on definite time charac-
teristic, operating time 0.5...100 min
Two phase unbalance protection stage
∆
I
1
>
and stage
∆
I
2
>. Stage
∆
I
1
>: setting range
1.0...100 %
∆
I
n
, based on definite time charac-
teristic, operating time 1.0...300 s. Stage
∆
I
2
>:
setting range 2.0...80 %
∆
I
n
, based on an in-
verse time characteristic, setting range 0.1...1.0
for time multiplier k
∆
2
Undercurrent protection I< for detection of
capacitor disconnection, setting range 0.10...
0.70 x I
n
. I< operates with a definite time char-
acteristic, range 1.0...100 s. Reconnection time
setting t
rec
for complete capacitor discharging
is 0.5...100 min
Compensation for natural unbalance current
within the setting 0...20 %
∆
I
n
Digital display of measured and set values and
sets of data recorded at the moment when a fault
occurs
All settings may be keyed in using the push-
buttons of the front panel or they may be set
using a personal computer
Continuous self-supervision including both
hardware and software. At a permanent fault
the alarm output relay operates and the other
outputs are blocked
1MRS 750065-MUM EN
Issued 96-04-12
Modified 99-10-18
Version D
Checked GL
Approved YK
Data subject to change without notice