background image

Ethernet Adapter

SPA-ZC 402

1MRS755479

Technical data (cont´d)

6

RoHS Compliance

Radio frequency interference tests

Conducted, common mode

Radiated, amplitude-modulated

Radiated, pulse-modulated

According to the IEC 61000-4-6 and
IEC 60255-22-6

10 V (rms), f = 150 kHz ... 80 MHz

According to the IEC 61000-4-3 and
IEC 60255-22-3

10 V/m (rms), f = 80 ... 2700 MHz

According to the ENV 50204 and
IEC 60255-22-3

10 V/m, f = 900 MHz

Fast transient disturbance tests

All terminals

According to the IEC 60255-22-4 and
IEC 61000-4-4

4 kV

Surge immunity test

Power supply SPA-ZC402xxxA

Power supply SPA-ZC402xxxC

RJ-45 cable

According to the IEC 60255-22-5 and IEC 61000-4-5

4 kV, line to earth
2 kV, line to line
2 kV, line to earth
1 kV, line to line
2 kV, line to earth

Power frequency (50 Hz) magnetic field 

According to the IEC 61000-4-8

300 A/m continuous

Electromagnetic emission tests

Conducted, RF-emission (Mains term.)

Radiated RF-emission

According to the EN 55011
EN 55011, class A, IEC 60255-25
EN 55011, class A, IEC 60255-25

CE compliance

Complies with the EMC directive 2004/108/EC and the LV 
directive 2006/95/EC

Standard tests

Mechanical tests
Vibration tests (sinusoidal)
Shock and bumb test

According to the IEC 60255-21-1, class I
According to the IEC 60255-21-2, class I

Auxiliary power supplies

Type 

SPA-ZC 402 xxxA

SPA-ZC 402 xxxC

Input voltage AC

110/120/220/240 V

-

Input voltage DC

110/125/220 V

24/48/64 V

Voltage variation

AC 85...110%, DC 80...120% of 
rated value

DC 80.120% of rated value

Burden

<4W

Ripple in DC auxiliary voltage

max. 12% of rated DC value (IEC 60255-11)

Interruption time in auxiliary DC 
voltage without resetting

110 V < 40ms

24 V < 24ms

Electromagnetic compatibility tests

Complies with the RoHS directive 2002/95/EC