![ABB SPA-ZC 302 Installation And Commissioning Manual Download Page 63](http://html.mh-extra.com/html/abb/spa-zc-302/spa-zc-302_installation-and-commissioning-manual_3588063.webp)
1MRS755014
SPA-ZC 302
63
Profibus-DPV1/SPA Gateway
Installation and Commissioning Manual
Fig. 8.3.1.-2
SPA LED indicators
See Table 8.3.1-2 for the description of the Profibus LED indicators pictured in
Fig. 8.3.1.-2 .
8.4.
Troubleshooting
When troubleshooting the gateway, first check the LED indicators described in
Section 8.3. Self-diagnosis. If there is a LED flashing, a coarse error can be located
through the flashing pattern of the LED.
8.4.1.
Gateway diagnostics
Detailed information about the error may be available in the diagnostics that can be
uploaded from the gateway. For details about uploading, see Section 5.4.2.3. Upload
diagnostics.
SPA
STATUS
SPA
RS485
RS232
TTL
1
2
SPA_LED_a
Table 8.3.1-2
SPA LED indicator description
LED no Description
Colour State
Indicates
Off
No power to the gateway.
Green
Flashing 1 Hz
Power ON. Running in configuration mode.
1
Module Status
On
Power ON. Running in application mode.
Red
Flashing 1 Hz
Configuration error. Test of the onboard configuration file failed
(gateway not operational).
On
Hardware error (Flash, SRAM, ABS).
Off
SPA/Cfg Communication Idle.
Green
Flashing irregular
Serial Message Transmission when in Application mode (Until SPA
goes on-line) and when in configuration mode.
SPA
On
SPA Network on-line.
2
Communication
Flashing irregular
Serial message reception error when in both application and
configuration mode
Status
Red
(framing, parity, CRC error etc.).
On
No SPA slave attached or cabling problem (SPA Network Offline).