7.3.5
Settings
PID-4144-SETTINGS v6
Table 13:
BINSTATREP Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
t
0.0 - 60.0
s
0.1
10.0
Time delay of function
7.3.6
Operation principle
GUID-537921CA-82B9-4A02-BAD1-67E3AC61AE96 v3
The Logical signal status report (BINSTATREP) function has 16 inputs and 16
outputs. The output status follows the inputs and can be read from the local HMI or
via SPA communication.
When an input is set, the respective output is set for a user defined time. If the
input signal remains set for a longer period, the output will remain set until the
input signal resets.
t
t
INPUTn
OUTPUTn
IEC09000732-1-en.vsd
IEC09000732 V1 EN-US
Figure 8:
BINSTATREP logical diagram