52
SensyMaster FMT230, FMT250
THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C
… 8 Commissioning and operation
… Parameterization of the device
Parameterization via the local operating interface
A PC / notebook and the USB interface cable are needed to
configure the device via the device local operating interface
(3KXS310000L0001).
1
Local operating interface
2
Programming plug
3
PC / Notebook
4
USB-interface cable
Figure 50: Connection to the local operating interface
Connection on the device
1. Open device terminal box.
2. Connect programming plug to the local operating interface
of the device.
3.
Insert USB interface cable into a free USB female connector
on the PC / notebook.
Note
Any required drivers are automatically installed by Windows®. If
installation of the drivers does not start automatically, search
for the drivers via the Windows driver search. In case of no
internet connection, use the ‘Prolific driver’ from the software
package.
4.
Switch on the device power supply.
5. Conduct parameterization of the device.
Installation of the ABB Field Information Manager (FIM)
A software package is available for configuration:
• ABB Field Information Manager (FIM) combined with the
ABB SensyMaster Field Device Information Package (FDI
package).
Field Information Manager (FIM) with the ABB SensyMaster
Field Device Information Package
Download the ABB Field Information Manager (FIM)
using the adjacent download link.
Download the ABB FDI package using the adjacent
download link.
Installation of the software and connection to the flowmeter:
1.
Install ABB Field Information Manager (FIM).
2.
Unpack the ABB FDI package into the c:\temp folder.
3.
Connect the flowmeter with the PC / laptop, see Connection
on the device on page 52.
4.
Power-up the power supply for the flowmeter and start the
ABB Field Information Manager (FIM).
5.
Drag and drop the ‘ABB.FMT2xx_FMT4xx.01.00.01.HART.fdix’
file (or newer version) to the ABB Field Information Manager
(FIM). No special view is needed for this.
6.
Right-click
1
as shown in Figure 51.
Figure 51: Select FIM – ‘Device Settings’
7.
Select ‘DEVICE SETTINGS’
2