ABB SACE
SACE PR010/T
RH0029002
L2551
6/67
67
2.1
Operation mode menu tree
2.2
Indications on operation
• The SACE PR010/T unit can be used only with SACE PR212/P and SACE PR212/P-LSIG
protection releases with test connectors on the front.
• The automatic test and the manual test with default parameters may be performed only by
turning the protection release to electronic SET with the dip switch provided.
• The manual test may be performed either with electronic SET or with manual SET. In the case
of manual test with manual SET, thresholds and curves must be selected with the dip-switches
1
2
3
4
5
6
7
8
9
Op
eratio
n mo
de
7. Select
DUT
(PR212
/P
)
1.
T
est
1. Protections
1. Automatic
Start test (select SET ELT)
Crea
te
repor
t
2. Manual
1. Default
setting
Start test
2. User setting
Set parameters Start test
2. Re
adin
g
1.Ammeter
Read currents
2. Config./Param.
1. DUT
configuration and
param.
1. Manual
parameters
Display DUT configuration and
parameters
2. Electronic
parameters
Display DUT configuration and
parameters
2. Default
parameters
1. Only for test
Display default configuration
and parameters
2. Operative
Display default configuration
and parameters
3. Information
Read release identification, SW version and Serial Number
4. Tripping
parameters
Display tripping parameters
3. Prog
ramm
ing
1. Change DUT
parameters
1. DUT config.
Change DUT configuration parameters
2. DUT parameters
(ELT)
Change DUT protection parameters
2. Default
parameters
Program DUT with default parameters for normal operation
3. Def. default
parameters
1. Only for test
Define DUT protection parameters
2. Operative
Define DUT protection parameters
Test connector