1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
31
Table 4.2.1-3
Digital inputs
Type
PS_87H
(REX521xxHxx)
PS_87L
(REX521xxLxx)
Operating range, dc
80…265 V dc
(for DI9 18...265 V)
18...265 V
Input voltage, dc
110/125/220 V (for DI9
also 24/48/60 V)
24/48/60/110/125/220 V
Current drain
~2…25 mA
Power consumption/input
<0.8 W
Table 4.2.1-4
Signal outputs
Max system voltage
250 V ac/dc
Continuous carry
5 A
Make and carry for 0.5 s
10 A
Make and carry for 3 s
8 A
Breaking capacity when control circuit time-
constant L/R <40 ms, at 48/110/220 V dc
1 A/0.25 A/0.15 A
Table 4.2.1-5
Power outputs
Max system voltage
250 V ac/dc
Continuous carry
5 A
Make and carry for 0.5 s
30 A
Make and carry for 3 s
15 A
Breaking capacity when control circuit time
constant L/R <40 ms, at 48/110/220 V dc
5 A/3 A/1 A
Minimum contact load
100 mA, 24 V ac/dc (2.4 VA)
TCS (Trip-circuit
supervision)
Control voltage range
20…265 V ac/dc
Current drain through
the supervision circuit
approx. 1.5 mA (0.99…1.72 mA)
Minimum voltage
(threshold) over a
contact
20 V ac/dc (15…20 V)
Table 4.2.1-6
Environmental conditions
Specified service temperature range
-10…+55
°
C
Transport and storage temperature range
-40…+70
°
C
Enclosure class
Front side, flush-mounted
IP 54
Rear side, connection terminals
IP 20
Dry heat test
according to IEC 60068-2-2
Dry cold test
according to IEC 60068-2-1
Damp heat test, cyclic
according to IEC 60068-2-30,
r.h. = 95%, T = 25…55
°
C
Storage temperature tests
according to IEC 60068-2-48