1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
51
Table 11.5.-1Class 1 data signals
Function block
IEC name
St
Ftyp
Inf
Num
GI
Typ
COT
Function block
(ABB name)
Io>
Non-directional earthfault general START
A
160
67
1
2
1, 9
NEF1Low
Io>
Non-directional earthfault TRIP>
A
160
92
0
2
1
NEF1Low
Io>>
Non-directional earthfault TRIP>>
A
160
93
0
2
1
NEF1High
Io>>
Non-directional earthfault START>>
P
162
95
1
1
1, 9
NEF1High
Io>>>
Non-directional earthfault START>>>
P
162
97
1
1
1, 9
NEF1Inst
Io>>>
Non-directional earthfault TRIP>>>
P
162
99
0
1
1
NEF1Inst
Io>-->
Directional earthfault general START
P
163
67
1
1
1, 9
DEF2Low
Io>-->
Directional earthfault TRIP>
P
163
92
0
1
1
DEF2Low
Io>>-->
Directional earthfault TRIP>>
P
163
93
0
1
1
DEF2High
Io>>-->
Directional earthfault START>>
P
163
95
1
1
1, 9
DEF2High
Io>>>-->
Directional earthfault START>>>
P
163
97
1
1
1, 9
DEF2Inst
Io>>>-->
Directional earthfault TRIP>>>
P
163
99
0
1
1
DEF2Inst
3I>
Non-directional overcurrent general START
A
160
84
1
2
1, 9
NOC3Low
3I>
Non-directional overcurrent TRIP>
A
160
90
0
2
1
NOC3Low
3I>>
Non-directional overcurrent TRIP>>
A
160
91
0
2
1
NOC3High
3I>>
Non-directional overcurrent START>>
P
162
94
1
1
1, 9
NOC3High
3I>>>
Non-directional overcurrent START>>>
P
162
96
1
1
1, 9
NOC3Inst
3I>>>
Non-directional overcurrent TRIP>>>
P
162
98
0
1
1
NOC3Inst
3I>->
Directional overcurrent general START
P
164
84
1
1
1, 9
DOC6Low
3I>->
Directional overcurrent TRIP>
P
164
90
0
1
1
DOC6Low
3I>>->
Directional overcurrent START>>
P
164
94
1
1
1, 9
DOC6High
3I>>->
Directional overcurrent TRIP>>
P
164
91
0
1
1
DOC6High
3I2f>
Inrush START
P
167
84
1
1
1, 9
Inrush3
3Ith>
Thermal overload (cables) START
P
168
84
1
1
1, 9
TOL3Cab
3Ith>
Thermal overload (cables) TRIP>
P
168
90
0
1
1
TOL3Cab
3Ith>
Thermal overload (cables), Current alarm
P
168
19
0
1
1
TOL3Cab
Iub>
Current unbalance START
P
173
84
1
1
1, 9
CUB3Low
Iub>
Current unbalance TRIP>
P
173
90
0
1
1
CUB3Low
Master trip signal
P
10
221
0
1
1
system
External trip signal
P
10
222
0
1
1
system
Lockout
P
10
223
0
1
1
system
Breaker failure
A
*)
85
0
1
1
**)
0-->I
AR sequence successful
A
*)
128
0
1
1
AR5Func
0-->I
AR interrupted
A
*)
130
0
1
1
AR5Func
0-->I
AR in use/ not in use
A
*)
16
1
1
1, 9
AR5Func
0-->I
AR: change in CB position
B
240
180
0
1
1
AR5Func
0-->I
AR shot1
P
169
101
0
1
1
AR5Func
0-->I
AR shot 2
P
169
102
0
1
1
AR5Func
0-->I
AR shot 3
P
169
103
0
1
1
AR5Func
0-->I
AR shot 4
P
169
104
0
1
1
AR5Func
0-->I
AR shot 5
P
169
105
0
1
1
AR5Func
0-->I
AR shot 1 successful
P
169
111
0
1
1
AR5Func
0-->I
AR shot 2 successful
P
169
112
0
1
1
AR5Func
0-->I
AR shot 3 successful
P
169
113
0
1
1
AR5Func
0-->I
AR shot 4 successful
P
169
114
0
1
1
AR5Func
0-->I
AR shot 5 successful
P
169
115
0
1
1
AR5Func
0-->I
AR sequence
P
169
120
0
1
1
AR5Func
0-->I
AR: final trip
P
169
121
0
1
1
AR5Func
0-->I
AR: def. trip alarm
P
169
150
0
1
1
AR5Func