30
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
• optically isolated serial communication port
$GGLWLRQDOIHDWXUHVRIWKHGLVSOD\
• contrast adjustment with temperature compensation
• backlight control
4.1.15.
Indication LEDs
The relay is provided with three indication LEDs (green, yellow and red). With
latching/non-latching, steady/blinking light the LEDs indicate different states and
operations of the relay. For more information, refer to Operator’s Manual.
4.2.
Design description
4.2.1.
Technical data
Table 4.2.1-1
Energizing inputs
Rated frequency
50.0/60.0 Hz
Current inputs
rated current
0,2 A/1 A/5 A
Thermal withstand
capability
continuously
1.5 A/4 A/20 A
for 1 s
20 A/100 A/500 A
dynamic current withstand, half-wave value
50 A/250 A/1250 A
input impedance
<750 m
Ω
/<100m
Ω/
<20 m
Ω
Voltage inputs
rated voltage
100 V/110 V/115 V/120
V (parametrization)
voltage withstand, continuous
2 x U
n
(240 V)
burden at rated voltage
<0.5 VA
Sensor inputs
voltage range RMS
9.4 V RMS
voltage range peak
± 12 V
input impedance
>4.7 M
Ω
input capacitance
<1 nF
Table 4.2.1-2
Auxiliary power supplies
Type
PS_87H
(REX521xxHxx)
PS_87L
(REX521xxLxx)
Input voltage, ac
110/120/220/240 V
-
Input voltage, dc
110/125/220 V
24/48/60 V
Operating range
ac 85…110%, dc 80…120% of
rated value
dc 80…120% of rated value
Burden
<20 W
Ripple in dc auxiliary voltage
max. 12% of the dc value
Interruption time in auxiliary dc
voltage without resetting
<50 ms, 110 V and
<100 ms, 200 V
<20 ms, 24 V and
<100 ms, 48 V
Internal overtemperature
indication
+78
°
C (+75…+83
°
C)