9.4.7.2
Operate time of the overexcitation protection
The operate time of OEXPVPH is a function of the relative overexcitation.
The so called IEEE law approximates an inverse-square law and has been chosen
based on analysis of the various transformer overexcitation capability characteristics.
They match the transformer core capability well.
The inverse-square law is according to equation
op
2
2
0.18
0.18
t
M
1
V Hz>
k
k
overexcitation
×
×
=
-
=
æ
ö
ç
÷
è
ø
IECEQUATION2298 V2 EN
(Equation 81)
where:
M
the relative excitation
V/Hz> Operate level of over-excitation function at no load in % of (UBase/f
rated
)
k
is time multiplier for inverse time functions, see figure
.
The relative excitation M is calculated using equation
measured
measured
rated
measured
measured
rated
M
U
U
f
f
UBase
UBase f
f
=
=
×
æ
ö
ç
÷
è
ø
æ
ö
ç
÷
è
ø
IECEQUATION2404 V1 EN
(Equation 82)
Inverse delays as per figure
, can be modified (limited) by a special definite delay
setting
tMin
Section 9
1MRK 504 135-UEN A
Voltage protection
226
Technical manual