27. Functions, codes and symbols
Table 68. RET615 functions, codes and symbols
Function
IEC 61850
IEC 60617
IEC-ANSI
Protection
Three-phase non-directional overcurrent protection, low
stage
PHLPTOC1
3I> (1)
51P-1 (1)
PHLPTOC2
3I> (2)
51P-1 (2)
Three-phase non-directional overcurrent protection,
high stage
PHHPTOC1
3I>> (1)
51P-2 (1)
PHHPTOC2
3I>> (2)
51P-2 (2)
Three-phase non-directional overcurrent protection,
instantaneous stage
PHIPTOC1
3I>>> (1)
50P/51P (1)
PHIPTOC2
3I>>> (2)
50P/51P (2)
Non-directional earth-fault protection, low stage
EFLPTOC1
Io> (1)
51N-1 (1)
EFLPTOC2
Io> (2)
51N-1 (2)
Non-directional earth-fault protection, high stage
EFHPTOC1
Io>> (1)
51N-2 (1)
EFHPTOC2
Io>> (2)
51N-2 (2)
Negative-sequence overcurrent protection
NSPTOC1
I2> (1)
46 (1)
NSPTOC2
I2> (2)
46 (2)
Residual overvoltage protection
ROVPTOV1
Uo> (1)
59G (1)
ROVPTOV2
Uo> (2)
59G (2)
Three-phase undervoltage protection
PHPTUV1
3U< (1)
27 (1)
PHPTUV2
3U< (2)
27 (2)
Three-phase overvoltage protection
PHPTOV1
3U> (1)
59 (1)
PHPTOV2
3U> (2)
59 (2)
Three-phase thermal overload protection for power
transformers, two time constants
T2PTTR1
3Ith>T
49T
Stabilized and instantaneous differential protection for
2W transformers
TR2PTDF1
3dI>T
87T
Numerical stabilized low impedance restricted earth-
fault protection
LREFPNDF1
dIoLo>
87NL
High impedance based restricted earth-fault protection
HREFPDIF1
dIoHi>
87NH
Circuit breaker failure protection
CCBRBRF1
3I>/Io>BF
51BF/51NBF
Master trip
TRPPTRC1
Master Trip (1)
94/86 (1)
TRPPTRC2
Master Trip (2)
94/86 (2)
Arc protection
ARCSARC1
ARC (1)
50L/50NL (1)
ARCSARC2
ARC (2)
50L/50NL (2)
ARCSARC3
ARC (3)
50L/50NL (3)
Transformer Protection and Control
1MRS756891 F
RET615
Product version: 4.0
62
ABB
Summary of Contents for RET615
Page 1: ...Relion 615 series Transformer Protection and Control RET615 Product Guide...
Page 65: ...65...
Page 66: ......