Table 41. Thermal overload for protection, two time constants (T2PTTR) main settings
Parameter
Function
Value (Range)
Step
Temperature rise
T2PTTR
0.0...200.0
o
C
0.1
Max temperature
T2PTTR
0.0...200.0
o
C
0.1
Operate temperature
T2PTTR
80.0...120.0 %
0.1
Weighting factor p
T2PTTR
0.00...1.00
0.01
Short time constant
T2PTTR
6...60000 s
1
Current reference
T2PTTR
0.05...4.00 x I
n
0.01
Operation
T2PTTR
Off
On
-
Table 42. Transformer differential protection of two-winding transformers (TR2PTDF)
Characteristic
Value
Operation accuracy
Depending on the frequency of the current measured: f
n
±2 Hz
±3.0% of the set value or ±0.002 x I
n
Operate time
1)2)
Minimum
Typical
Maximum
Low stage
High stage
34 ms
21 ms
40 ms
22 ms
44 ms
24 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Suppression of harmonics
DFT: -50 dB at f = n x f
n
, where n = 2, 3, 4, 5, …
1)
Current before fault = 0.0, f
n
= 50 Hz, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the output contact. When differential current = 2 x set operate value and f
n
= 50 Hz.
Transformer Protection and Control
1MRS756891 F
RET615
Product version: 4.0
ABB
41