Section 3
1MAC309294-MB F
Basic functions
60
RER620
Technical Manual
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate state.
The default value (0) is used if VALID output indicates invalid status.
3.9.5.3
Signals
Table 47:
GOOSERCV_INTL Input signals
Table 48:
GOOSERCV_INTL Output signals
3.9.6
GOOSERCV_CMV function block
3.9.6.1
Function block
Figure 14:
function block
3.9.6.2
Functionality
The GOOSERCV_CMV function is used to connect GOOSE measured value inputs to the
application. The MAG_IN (amplitude) and ANG_IN (angle) inputs are defined in the
GOOSE configuration (PCM600).
The MAG output passes the received GOOSE (amplitude) value for the application.
Default value (0) is used if VALID output indicates invalid status.
The ANG output passes the received GOOSE (angle) value for the application. Default
value (0) is used if VALID output indicates invalid status.
3.9.6.3
Signals
Table 49:
GOOSERCV_CMV Input signals
Name
Type
Default
Description
IN
Dbpos
00
Input signal
Name
Type
Description
OP
BOOLEAN
Position open output signal
CL
BOOLEAN
Position closed output signal
OK
BOOLEAN
Position OK output signal
VALID
BOOLEAN
Output signal
GOOSERCV_CMV
MAG
ANG
VALID
Name
Type
Default
Description
MAG_IN
FLOAT32
0
Input signal (amplitude)
ANG_IN
FLOAT32
0
Input signal (angle)
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......