5.9.1
General settings
IEC-104 gateway enabled
enables or disables the IEC 60870-5-104 to IEC
60870-5-101 gateway.
Table 7:
IEC-104 gateway enabled
Description
Value
Type
Boolean
Units
N/A
Value range
No, Yes
Note
-
5.9.2
Serial settings
The serial settings define the physical serial communication properties between the
device and an IEC 60870-5-101 slave. The selection between RS-232, RS-422 and
RS-485 is made with the DIP switches located below the RS2 serial port.
The IEC-101 devices can be connected to the serial ports RS1 or RS2 (single
device per port). When the serial port RS1 is used, the console switch below the
RS1 should be in the “Data” position.
The settings for the IEC-104 gateway applications are available on WEB user
interface applications IEC-104 (RS1) and IEC-104 (RS2).
GUID-ADB6008D-9F4F-44EB-A13F-799CC98EFBCD V1 EN
Figure 31:
Serial settings
Speed (bps)
defines the IEC 60870-5-101 serial communication speed (bps).
Table 8:
IEC 60870-5-101 serial communication speed (bps)
Description
Value
Type
Serial speed
Units
Bits per second
Value range
1200, 2400, 4800, 9600, 19200, 38400, 57600
Note
-
Data bits
defines the number of data bits used in the IEC-101 serial communication.
Section 5
1MRS757105 B
RER601/603 Configurator
46
RER601/603
Technical Manual