A070590 V5 EN
Figure 12:
Mounting the case
5.
Tighten the M5 screws.
The allowed range for the fixing screws’ tightening torque is
0.7...1 Nm.
6.
Attach the protective film back on the top side of the case.
7.
Install the plug-in unit into the case.
The purpose of the protective film is to prevent debris falling inside the unit while
installing electrical wiring. Remove the protective film before energizing the
protection relay.
1MRS757799 C
Section 4
Mounting
REC615 and RER615
23