AIM0017
A071232 V5 EN
Figure 29:
Example of AIM0017 card variant (4 I with 0.2/1 A Io channel)
5.4.2
Connecting current and voltage sensor signalling inputs
•
Connect the wires from the sensors to the correct device according to the phase
order and the connection diagram.
•
Select either sensor or voltage transformer mode for SIM0001 card.
•
For sensor mode, each terminal of a sensor is dimensioned for maximum of
2.5 mm
2
wire.
•
For voltage transformer mode, each terminal of a voltage transformer is
dimensioned for one 0.5...0.6 mm
2
wire or two wires of maximum 2.5
mm
2
.
The SIM0002 card for REC615 is provided with one current input terminal for a
maximum of 2.5 mm
2
wire and three RJ-45 type connectors which are intended for the
current and the voltage sensor signalling inputs.
For more information, see the specific card variants in the application
engineering guide.
1MRS757799 C
Section 5
Connecting
REC615 and RER615
39
Installation Manual