Negative sequence inverse time characteristic
Negative sequence current
T
im
e
de
la
y
I2
tMax
tMin
IEC08000355-2-en.vsd
1
10
100
1000
10000
0.01
0.1
1
10
100
IEC08000355 V2 EN
Figure 202:
Inverse Time Delay characteristic, step 1
indicates that the protection function has a set minimum
operating time
t1Min
of 5 sec. The setting
t1Min
is freely settable and is used as a
security measure. This minimum setting assures appropriate coordination with for
example line protections. It is also possible to set the upper time limit,
t1Max
.
9.12.3.2
Start sensitivity
The trip start levels Current
I2-1>
and
I2-2>
of NS2PTOC are freely settable over a
range of 3 to 500 % of rated generator current
IBase
. The wide range of start setting
is required in order to be able to protect generators of different types and sizes.
After start, a certain hysteresis is used before resetting start levels. For both steps the
reset ratio is 0.97.
9.12.3.3
Alarm function
The alarm function is operated by START signal and used to warn the operator for an
abnormal situation, for example, when generator continuous negative sequence
current capability is exceeded, thereby allowing corrective action to be taken before
removing the generator from service. A settable time delay
tAlarm
is provided for the
alarm function to avoid false alarms during short-time unbalanced conditions.
Section 9
1MRK 502 071-UEN -
Current protection
392
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...