Disable the Web browser proxy settings or make an exception to the
proxy rules to allow the IED's WHMI connection, for example, via
Internet Options/Connections/LAN Settings/Advanced/Exceptions
.
1.
To enable the WHMI, select
Main menu/Configuration/HMI/Web HMI mode
via the LHMI.
2.
Reboot the IED for the change to take effect.
For more information on the WHMI, see the operation manual.
4.11
IED User Management
IED user authorization is disabled by default and can be enabled at
Main Menu/
Configuration/Authorization
in LHMI or WHMI. IED user passwords can be
changed in LHMI and using the IED User Management tool in PCM600.
GUID-FC9D4AB3-C472-4BDB-B64B-DEE4FEACC4FA V1 EN
Figure 32:
Changing the password using the IED User Management tool
If the remote authentication has been enabled, changes have to be made in PCM600 to
make the communication between the IED and PCM600 work.