Table 46. Phase discontinuity protection (PDNSPTOC)
Operation accuracy
Depending on the frequency of the current
measured: fn ±2Hz
±2% of the set value
Start time
< 70 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Operate time accuracy in definite
time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50dB at f = n x fn, where n = 2, 3, 4, 5,…
Table 45. Negative phase-sequence current protection (NSPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
NSPTOC
0.01...5.00 x I
n
0.01
Time multiplier
NSPTOC
0.05...15.00
0.05
Operate delay time
NSPTOC
40...200000 ms
10
Operating curve type
1)
NSPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10,
11, 12, 13, 14, 15, 17, 18, 19
1) For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
Table 47. Phase discontinuity protection (PDNSPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
(Current ratio setting I
2
/I
1
)
PDNSPTOC
10...100 %
1
Operate delay time
PDNSPTOC
100...30000 ms
1
Min phase current
PDNSPTOC
0.05...0.30 x In
0.01