Feeder Protection and Control
REF615
Product version: 2.0
1MRS756379 D
Table 36. Three-phase undervoltage protection (PHPTUV)
Operation
accuracy
Depending on the frequency of the voltage measured: f
n
±2Hz
±1.5% of the set value or ±0.002 x U
n
Start time
1) 2)
Minimum
Typical
Maximum
U
Fault
= 0.9 x set
Start value
62 ms
64 ms
66 ms
Reset time
< 40 ms
Reset ratio
Depends on the set
Relative hysteresis
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20
ms
3)
Suppression of harmonics
DFT: -50dB at f = n x f
n
,
where n = 2, 3, 4, 5,…
Table 37. Three-phase undervoltage protection (PHPTUV) main settings
Parameter
Function
Value (Range)
Step
Start value
PHPTUV
0.05...1.20 x U
n
0.01
Time multiplier
PHPTUV
0.05...15.00
0.05
Operate delay time
PHPTUV
60...300000 ms
10
Operating curve type
1)
PHPTUV
Definite or inverse time
Curve type: 5, 15, 21, 22, 23
1)
Start value
= 1.0 x U
n
, Voltage before fault 1.1 x U
n
, f
n
= 50 Hz, undervoltage in one phase-to-phase with nominal
frequence injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Minimum
Start value
= 0.50,
Start value
multiples in range of 0.90 to 0.20
1) For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
Table 38. Positive sequence undervoltage protection (PSPTUV)
Operation
accuracy
Depending on the frequency of the voltage measured: f
n
±2Hz
±1.5% of the set value or ±0.002 x U
n
Start time
1) 2)
Minimum
Typical
Maximum
U
Fault
= 0.99 x set
Start value
51 ms
53 ms
54 ms
U
Fault
= 0.9 x set
Start value
43 ms
45 ms
46 ms
Reset time
< 40 ms
Reset ratio
Depends on the set
Relative hysteresis
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50dB at f = n x f
n
,
where n = 2, 3, 4, 5,…
1)
Start value
= 1.0 x U
n
, Positive sequence voltage before fault 1.1 x U
n
, f
n
= 50 Hz, positive sequence undervoltage
with nominal frequence injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact