ABB
27
Feeder Protection and Control
REF615
Product version: 2.0
1MRS756379 D
Table 30. Directional EF protection (DEFxPDEF)
Operation
accuracy
Depending on the frequency of the current measured: f
n
±2Hz
DEFLPDEF
Current:
±1.5% of the set value or ±0.002 x I
n
Voltage:
±1.5% of the set value or ±0.002 x U
n
Phase angle:
±2°
DEFHPDEF
Current:
±2% of the set value or ±0.003 x I
n
(at currents in the range of 0.1…10 x I
n)
±5.0% of the set value
(at currents in the range of 10…40 x I
n)
Voltage:
±1.5% of the set value or ±0.01 x U
n
Phase angle:
±2°
Start time
1) 2)
Minimum
Typical
Maximum
DEFHPDEF and
DEFLPDEF:
I
Fault
= 2 x set
Start value
61 ms
64 ms
66 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
RMS: No suppression DFT: -50dB at f =
n x f
n
, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
1) Set
Operate delay
time
= 0,06 s,
Operate curve type
= IEC definite time,
Measurement mode
= default (depends
on stage), current before fault = 0.0 x In, fn = 50 Hz, earth-fault current with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum
Start value
= 2.5 x In,
Start value
multiples in range of 1.5 to 20