such as string values, are restored to the original value only after a reboot even though
the edited value is not stored in the flash memory.
1.
Click
Write to IED
after editing parameter values to put the values into
protection relay's database for use.
GUID-88D8CBAE-BC8A-4036-AB47-75653D813073 V1 EN
Figure 45:
Writing values to protection relay
The values are not stored to the flash memory.
2.
Click
Commit
to write the values to the flash memory.
•
Click
Reject
to cancel saving settings.
•
If the parameter has an edit-copy, the original parameter value is
restored.
•
If the parameter does not have an edit-copy, the edited parameter
value remains visible until the protection relay is rebooted.
However, the edited value is not stored in the nonvolatile memory
and thus the reboot restores the original value.
GUID-24B2A9CD-DE5A-4DA0-8B57-18BA7B9E8BF9 V2 EN
Figure 46:
Committing changes
1MRS758754 B
Section 4
Using the HMI
REC615 and RER615
67
Operation Manual