Activate or deactivate an output signal for protection or other function to test the
function.
1.
Select
Main Menu/Tests/Function tests/Current protection/<function
block name>
and press
.
2.
Select the output signal to be activated or deactivated with
or
and press
.
3.
To deactivate all output signals for the function, select
Reset
with
or
and press
.
8.5.4
Selecting the internal fault test
The internal fault may be tested by using the LHMI. When enabling the test, the
internal relay fault output contact is activated, the green Ready LED is flashing and
internal fault test indication is shown on the LHMI. See the technical manual for the
internal relay fault output contact location. The internal fault can only be activated by
using the LHMI.
Differing from real internal fault situation, the other output contacts
are not released and locked during the test. In other words, protection
functions can operate and trip the outputs when the internal fault is
tested.
1.
Select
Main menu/Tests/IED test/Internal fault test
and press
.
A071156 V2 EN
Figure 99:
Internal fault test
2.
Select the value with
or
.
3.
Press
to confirm the selection.