1MRK 511 371-UEN
Section 3
IEC 60870-5-103
Communication Protocol Manual, IEC 60870-5-103
15
Distributed busbar protection REB500
3.4
ACC actual channel
The REB500 Bay Unit 500BU04 supports five voltage channels. Since, however,
the compatible range of the standard only lists four voltage channels, the fifth
channel is transferred to the private domain.
Assignment of REB500 channels to IEC 60870-5-103 channel numbers:
Table 14
IEC 60870-5-103 analog channel assignment
REB500 channel
designation
REB500
application
IEC 60870-5-103 channel designation
ACC (actual channel)
I1
I L1
1 = I L1
I2
I L2
2 = I L2
I3
I L3
3 = I L3
I4
I L0
4 = V L1
U1
U L1
5 = V L1E
U2
U L2
6 = V L3
U3
U L3
7 = V 0E
U4
U L0
8 = U L1
U5
U 5
64 = private
3.5
Generic REB500 functions
3.5.1
Diagnostic information
Status and diagnostic information is generated by the various REB500 application
software modules and transferred spontaneously as events every time the status
changes. A separate group exists for diagnostic information with an entry for every
subsystem of the REB500 system software REBSYS.
Diagnostic event group: