1MRK 511 371-UEN
Section 3
IEC 60870-5-103
Communication Protocol Manual, IEC 60870-5-103
23
Distributed busbar protection REB500
The following table gives an example of the ASDU 10 ‘Generic Data’ that is
transferred spontaneously for displaying the differential currents of a given bus
zone.
Table 32
TYPE IDENTIFICATION: Generic data
0
0
0
0
1
0
1
0
T
ype
I
dentification
10
DATA UNIT
1
0
0
0
0
0
0
1
V
ariable
S
tructure
Q
ualifier
SQ=1, SQ_No.= 1
IDENTIFIER
Spontaneous <1>
C
ause
O
f
T
ransmission
COT
REB500 CU
C
ommon
A
ddress of
A
SDU <0>
GEN <254>
Fun
ction Type
FUN
INFORMATI
ON
Read value of single entry <244>
Inf
ormation number
INF
OBJECT
<0>
Return
information
identifier
RII
{
1, 0, 0
}
Number of generic data sets
NGD
{
NO, COUNT, CONT
}
4B H
Generic identification number Group
01 H
Entry
<1 .. 32>
Current value <1>
Kind of description
KOD
DATA STRUCTURE
<23>
DATA TYPE
21
DATA SIZE
GDD
1,0
NUMBER
,
CONT
<12> M
EASUREMENT WITH QUALITY DESCRIPTOR
DATA TYPE
2
DATA SIZE
GDD 1
3,0
NUMBER
,
CONT
3 or 4 (including measurement L0)
OV ER RES
MVAL (4..8)
GID 1a
MVAL (9..16)
OV ER RES
MVAL (4..8)
GID 1b
MVAL (9..16)
OV ER RES
MVAL (4..8)
GID 1c
MVAL (9..16)
<14>
BINARY TIME
DATATYPE
7
DATASIZE
GDD 2
1,0
NUMBER
,
CONT
Time stamp (CP56Time2a)
GID 2
3.6
Special information and instructions for configuring
the control system
Private range
Provision is made in the event configuration (see Section 2.3) for the user to enter
his own private IEC 60870-5-103 definition for each REB500 signal.
The input fields for REB500 signals covered by the public part of the standard (see
Section 3.2) have a bright yellow back-ground their default setting ‘0’ for both IEC
function type and in-formation number. All other signals receive the presetting 0
for the IEC function type and the information number. A signal de-fined for
protocol 60870-5-103 that is not in the public range and has ‘0’ set for function
type and information number is transmit-ted via the generic part of the protocol.