IdMin
EndSection1
EndSection2
Restrain current
[ in pu of IBase]
Operate current
[ in pu of IBase]
SlopeSection2
SlopeSection3
en05000300.vsd
Operate
conditionally
IdMinHigh
A
C
B
IEC05000300 V1 EN-US
Figure 49: Overestimated charging current
If a high resistive fault is considered, the voltage in the fault location will not be much reduced.
Consequently, the value of the pre-fault “false” differential current will be a good estimation of
the actual charging current.
Subtracting the pre-fault charging current from the differential current under fault conditions
will make it possible to set
Idmin mainly without considering the charging current in order to
achieve maximum sensitivity. The stability at external faults will not be affected.
6.3.2.4
Time synchronization
M12022-66 v3
Time synchronization of sampled current values is a crucial matter in numerical line differential
protections. The synchronization is made with the so called echo method, which can be
complemented with GPS synchronization. In applications with symmetrical communication
delay, that is, send and receive times are equal, the echo method is sufficient. When used in
networks with asymmetrical transmission times, the optional GPS synchronization is required.
6.3.2.5
Analog signal communication for line differential protection
M12022-69 v6
Line differential protection uses digital 64 kbit/s communication channels to exchange
telegrams between the protection IEDs. These telegrams contain current sample values, time
information, trip signals, block signals, alarm signals and eight binary signals, which can be
used for any purpose. Each IED can have a maximum of four communication channels.
On a two terminal line there is a need of one 64 kbit/s communication channel provided that
there is only one CT in each line end, as shown in Figure
1MRK 505 343-UEN B
Section 6
Differential protection
119
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...