Power supply module (PSM)
INTERNAL FAIL
p1
+
-
Ready
Fail
+
Protective earth must be connected
EL
1MRK002801-AC-7-670-1.2-PG V3 EN-US
Figure 7:
Power supply module (PSM)
The auxiliary power wiring should have a minimum cross-sectional area of 1.0
mm
2
and a voltage rating of 250 V. Branch circuit protection must be provided in
the auxiliary power supply wiring to the IED, and if necessary it must be possible
to disconnect manually from the power supply. Fuse or circuit breaker up to 6 A
and 250 V should be close to the equipment.
Ensure that the IED is earthed before starting it.
5.3
Energizing the IED
GUID-E40DE80C-8DA4-4E17-876C-4CC3CE706347 v4
Before connecting the auxiliary power, check that the terminal strip is wired and
placed correctly. Remove the protective film from the top side of the unit.
During IED start-up, you can observe the following sequence:
1. The Green Ready LED starts to flash.
2. The LCD lights up and
starting...
is displayed.
3. The main menu is displayed. A final steady green Ready LED indicates a
successful start-up of the device.
If the self supervision of the IED detects a diagnostic error during the start-up
process, the green Ready LED flashes. Further information on the error may be
visible on the local HMI under
Main menu/Diagnostics/IED status/General
.
Note down the displayed information as reference when contacting ABB technical
support.
1MRK 500 129-UEN A
Section 5
Powering up the IED
670/650 series 2.2 IEC