![ABB Relion 670 series Installation Manual Download Page 97](http://html.mh-extra.com/html/abb/relion-670-series/relion-670-series_installation-manual_2448097.webp)
9.1.3
Flush mounting dimensions
M11571-3 v6
C
A
IEC04000465-3-en.vsd
B
E
D
IEC04000465 V3 EN-US
Figure 56:
Flush mounting
Case size
Tolerance
Cut-out dimensions (mm)
A
+/-1
B
+/-1
C
D
6U, 1/2 x 19"
210.1
254.3
4.0-10.0
13.5
6U, 3/4 x 19"
322.4
254.3
4.0-10.0
13.5
6U, 1/1 x 19"
434.7
254.3
4.0-10.0
13.5
E = 191.1 mm without rear protection cover, 231.8 mm with rear protection cover
1MRK 514 026-UEN B
Section 9
Technical data
670 series 2.2 IEC
91
Installation manual