Section 5
Mounting
5.1
Required tools
GUID-B9478208-286B-4CFF-9C47-074D641A6F71 v2
Generally, all the screws included in delivered mounting kits are of Torx type and a
torque screwdriver of the same type is needed (Tx10, Tx15, Tx20, Tx25 and
Tx30).
Use only the screws included in the mounting kit when mounting
the plates and the angles on the IED. Screws with wrong dimension
may damage the PCBs inside the IED.
5.2
Checking environmental conditions and mounting
space
GUID-2AF46E8C-25B3-4606-A768-E4B70E3D6B0A v10
The mechanical and electrical environmental conditions at the installation site must
be within the limits described in the technical manual and IEC60255-1, normal
environment.
•
Avoid installation in dusty, damp areas.
•
Check that sufficient space is available.
Sufficient space is needed at the front and rear of the IED to allow access to
wires and optical fibres and to enable maintenance and future modifications.
•
Ensure convection cooling around the case to minimize the heating effect
within the IED.
•
Avoid installation in dusty, damp places and where combustible
materials are present near the IED
5.3
Mounting the IED
M11978-3 v11
The IED can be rack, wall or flush mounted with the use of different mounting kits,
see figure
.
An additional box of type RHGS can be mounted to one side of a 1/2 or 3/4 IED.
The different mounting kits contain all parts needed including screws and assembly
instructions. The following mounting kits are available:
1MRK 514 026-UEN B
Section 5
Mounting
670 series 2.2 IEC
21
Installation manual