Table 13: Hint menu
Headline
Explanation
Incorrect setting of SyncLostMode
There are two explanations possible:
SyncLostMode is set to Block, no time source is
configured to achieve the required accuracy. Unless a
high accuracy time source is selected, the function
dependent on high time accuracy will be blocked.
SyncLostMode is set to BlockOnLostUTC, but there is
no UTC capable synch source (GPS, IRIG-B) used.
Unless a UTC capable time source is selected, the
function dependent on high time accuracy will be
blocked.
Sampled value substituted
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID:
<ABB_MU0101>
Time diff: IED vs Sampled value
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID:
<ABB_MU0101>
Frequency diff: IED vs Sampled value
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID:
<ABB_MU0101>
Invalid phase angle reference
The selected
PhaseAngleRef corresponds to an
analog channel that is not configured. Please
configure a valid reference channel.
GOOSE is configured on a disabled port
At least one of the access points configured for
GOOSE is disabled. The port can be disabled either
through changing the access point operation to off
or by unchecking the GOOSE protocol from the
access point in the Ethernet configuration in PCM600
or LHMI.
Please enable GOOSE on access points: AP_FRONT,
AP_1
LDCM not running the application image
<slot number> is running the factory image instead
of the application image. The factory image is older
and does not contain the latest updates and fixes.
Please reboot the IED. If the problem persists update
the LDCM firmware or replace the board.
LDCM version is not accepted
<device name> firmware version <version string> is
not accepted. The minimum accepted version is
<version string>.
Please update the LDCM firmware or replace the
board.
11.2.4
Hardware re-configuration
GUID-334C5D8B-F383-4CDE-9850-659ED6B405DC v1
When adding, removing or moving a hardware modules in an IED ( for example, I/O modules,
communication modules or time synchronization modules) a set of procedures must be
followed.
Adding a new module in to an IED
Procedure:
1MRK 505 385-UEN C
Section 11
Troubleshooting
Breaker protection REQ650
109
Commissioning manual