AccStopCurr set value. Only for a current lower than set AccStopCurr should activate
the output
POSOPEN
.
5.4. Check the circuit breaker is in
INVDPOS
if auxiliary contacts read same value or CB is
open and inject the current in selected phase more than
AccStopCurr set value.
6. Test of remaining life of CB
6.1. Test the set timing defined by
RatedOperCurr, RatedFltCurr, OperNoRated,
OperNoFault, DirCoef, CBLifeAlmLevel.
6.2. Vary the phase current in the selected phase from below rated operated current,
RatedOperCurr to above rated fault current, RatedFltCurr of a breaker.
6.3. The remaining life of CB output
CBLIFEPH
is estimated when the CB is changed from
closed to open position. Check that the output
CBLIFEPH
is decreased with a value
that corresponds to the injected current.
6.4.
CBLIFEAL
is activated as soon as
CBLIFEPH
is below the set
CBLifeAlmLevel value.
7.
Test of accumulated energy
7.1. Test the actual set values defined by
AccSelCal to Aux Contact, ContTrCorr and
AlmAccCurrPwr.
7.2. Inject phase current in the selected phase such that its value is greater than set
AccStopCurr value.
7.3. When the breaker goes to open position, accumulated energy
IPOWPH
is calculated.
The calculated value can be seen on the output
IPOWPH
.
7.4. Alarm signal
IPOWALPH
appears when
IPOWPH
is greater than set
AlmAccCurrPwr
value.
7.5. Lockout signal
IPOWLOPH
appears if
IPOWPH
exceeds further to the threshold value
LOAccCurrPwr.
7.6. Calculation of accumulated energy
IPOWPH
is stopped when injected current is lower
than set
AccStopCurr value.
8. Test of CB operation cycles
8.1. Test the actual set values defined by
OperAlmLevel and OperLOLevel.
8.2. The operation counter, NOOPER is updated for every close-open sequence of the
breaker by changing the position of auxiliary contacts
POSCLOSE and POSOPEN.
8.3.
OPERALM
is activated when NOOPER value exceeds the set
OperAlmLevel value. The
actual value can be read on the output
NOOPER
.
8.4.
OPERLO
is activated when NOOPER value exceeds the set
OperLOLevel value.
9. Test of CB spring charge monitoring
9.1. Test the actual set value defined by
SpChAlmTime.
9.2. Enable
SPRCHRST
input. Also activate SPRCHRD after a time greater than set time
SpChAlmTime.
9.3. At this condition,
SPCHALM
is activated.
10. Test of CB gas pressure indication
10.1. Test the actual set value defined by
tDGasPresAlm and tDGasPresLO.
10.2. The output
GPRESALM
is activated after a time greater than set time of
tDGasPresAlm value if the input
PRESALM
is enabled.
10.3. The output
GPRESLO
is activated after a set time of
tDGasPresLO value if the input
PRESLO
is enabled.
9.8.3.2
Completing the test
GUID-0A16206F-690E-46EF-86F4-5A89E0BF640B v3
1.
Continue to test another function or end the test by changing the
Test mode setting to
Off.
2.
Restore connections and settings to their original values if they were changed for testing
purposes.
1MRK 505 385-UEN C
Section 9
Testing functionality by secondary injection
Breaker protection REQ650
95
Commissioning manual
© Copyright 2017 ABB. All rights reserved