GUID-D2E0B8C9-6D5E-4032-9C38-805C2A19389B V1 EN
Figure 93:
Data set editor
1 Grid
2 Selection lists
3 List of data entries
1.
Select an IED node in the IEDs navigation pane.
2.
Click the
Datasets
tab in the editor pane.
3.
Right-click the area containing data set names and select
Insert new row
.
4.
Define the LN where the data set is to be placed (preselected
LD0/LLN0
is
recommended) and the name for the new data set.
5.
Click
Append>>
to add data items to the end of the data set or click
Insert>
to
add data items above the selected row in the data set entries list.
Reporting datasets can include status and measurement type of data. Also
configuration and setting values can be added to datasets in case required.
Above the data set entries list is shown how many attributes it is
possible to add to the data set and how many are already added.
Select a proper FC (functional constraint) value for the data attributes
to be added to a data set. If none is selected, that is “(all)” is shown on
the list, it is not possible to add attributes to the data set.
1MRS756800 F
Section 7
IEC 61850 communication engineering
630 series
121
Engineering Manual