Commands
Table 6:
Command push-buttons
Name
Description
Menu
•
Moving directly to Main menu, if
currently in any other menu or view.
•
Moving to the default view, if currently in
Main menu.
R/L
Changing the control position (remote or
local) of the device.
•
When the R LED is lit, remote control is
enabled and local control disabled.
•
When the L LED is lit, local control is
enabled and remote control disabled.
•
When none of the LEDs are lit, both
control positions are disabled.
Clear
•
Activating the Clear/Reset view.
Help
Showing the help menu.
Multipage
Opening alarm panel and selecting alarm
page from the view.
Function buttons
Table 7:
Function buttons
Name
Description
Function
button
Executing the defined function: OFF, menu short cut or binary control.
3.2.4
Local HMI functionality
3.2.4.1
Protection and alarm indication
Protection indicators
The protection indicator LEDs are Ready, Start and Trip.
The start and trip LEDs are configured via the disturbance recorder.
See the technical manual for more information on how to configure
and set the binary signals of the disturbance recorder.
Section 3
1MRS756509 E
630 series overview
22
630 series
Operation Manual