Section 4
IEC 60870-5-103 parameters and
diagnostics
4.1
Parameter list
The IEC 60870-5-103 parameters can be accessed with PCM600 or via the LHMI path
Configuration/Communication/IEC 60870-5-103/I3C0n
.
Some parameters are not visible in the “Basic” setting visibility mode.
To view all parameters use “Advanced” setting visibility mode in the
Parameter Setting tool in PCM600 and LHMI.
Table 14:
IEC 60870-5-103 settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
5=off
Selects if this protocol instance is enabled
or disabled
Serial port
1=COM 1
2=COM 2
1=COM 1
COM port
Address
1...255
1
1
Unit address
Start delay
0...20
char
1
4
Start frame delay in chars
End delay
0...20
char
1
4
End frame delay in chars
DevFunType
0...255
1
9
Device Function Type
UsrFunType
0...255
1
10
Function type for User Class 2 Frame
UsrInfNo
0...255
1
230
Information Number for User Class2
Frame
Class1Priority
0=Ev High
1=Ev/DR Equal
2=DR High
0=Ev High
Class 1 data sending priority relationship
between Events and Disturbance
Recorder data.
Class2Interval
0...86400
s
1
30
Interval in seconds to send class 2
response
Frame1InUse
-1=Not in use
0=User frame
1=Standard frame
1
2=Standard frame
2
3=Standard frame
3
4=Standard frame
4
5=Standard frame
5
6=Private frame 6
7=Private frame 7
6=Private frame 6
Active Class2 Frame 1
Table continues on next page
1MRS757647 C
Section 4
IEC 60870-5-103 parameters and diagnostics
620 series
31
Communication Protocol Manual