Parallel line out of service and not grounded
Z0m
A
OPEN
21
21
en05000223_ansi.vsd
CLOSED
OPEN
CLOSED
B
ANSI05000223 V1 EN
Figure 58:
Parallel line is out of service and not grounded
When the parallel line is out of service and not grounded, the zero sequence on that line
can only flow through the line admittance to the ground. The line admittance is high which
limits the zero-sequence current on the parallel line to very low values. In practice, the
equivalent zero-sequence impedance circuit for faults at the remote bus bar can be
simplified to the circuit shown in figure
The line zero sequence mutual impedance does not influence the measurement of the
distance protection in a faulty circuit. This means that the reach of the underreaching
distance protection zone is reduced if, due to operating conditions, the equivalent zero
sequence impedance is set according to the conditions when the parallel system is out of
operation and grounded at both ends.
A
B
C
IEC09000255_1_en.vsd
I
0
I
0
Z
0m
Z
0
-
Z
0m
Z
0m
Z
0
-
IEC09000255 V1 EN
Figure 59:
Equivalent zero-sequence impedance circuit for a double-circuit line with
one circuit disconnected and not grounded
The reduction of the reach is equal to equation
(
)
(
)
(
)
2
1
0
0
1
0
0
1
0
1
2
3
1
1
2
3
2
3
E
f
m
U
f
f
Z
Z
R
Z
K
Z
Z
Z
R
Z
Z
R
× × +
+
=
= -
× ×
+
+
× × +
+
EQUATION1284 V1 EN
(Equation 45)
Section 6
1MRK 506 334-UUS A
Impedance protection
124
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...