Indications
Chapter 8
Monitoring
2
Indications
2.1
Application
Use the indications list to view the state of binary signals during the fault. All binary input sig-
nals to the disturbance report function are listed.
2.2
Functionality
The indications list tracks zero-to-one changes of binary signals during the fault period of the
collection window. This means that constant logic zero, constant logic one or state changes from
logic one to logic zero will not be visible in the indications list. Signals are not time tagged. In
order to be listed in the indications list the:
1. signal must be connected to the DRP function blocks, (DRP1, DRP2, DRP3).
2. setting parameter, IndicationMask, for the input must be set to Show.
Output signals of other function blocks of the configuration will be listed by the signal name list-
ed in the corresponding signal list. Binary input signals are listed by the name defined in the con-
figuration.
The indications can be viewed on the local HMI and via SMS.
Summary of Contents for REL 551-C1*2.5
Page 1: ...Technical reference manual ProtectIT Line differential protection terminal REL 551 C1 2 5 ...
Page 23: ...14 Introduction to the technical reference manual Chapter 1 Introduction ...
Page 39: ...30 Technical data Chapter 2 General ...
Page 63: ...54 Blocking of signals during test BST Chapter 3 Common functions ...
Page 71: ...62 Line differential protection phase segregated DIFL Chapter 4 Line differential protection ...
Page 89: ...80 Thermal phase overload protection THOL Chapter 5 Current ...
Page 101: ...92 Event function EV Chapter 7 Logic ...
Page 163: ...154 Terminal diagrams Chapter 11 Diagrams Figure 39 REL 551 C1 with DC switch ...