33
Real-time clock with external time
synchronization (TIME)
Chapter 3
Common functions
Table 25:
Setting parameters for the time synchronization source selector function
1.5
Technical data
Table 26:
TIME - Time synchronisation
Parameter
Range
Default
Unit
Description
SYNCSRC
0-5
0
-
Selects the time synchronization source:
0: No source. Internal real time clock is
used without fine tuning.
1: LON bus
2: SPA bus
3: IEC 60870-5-103 bus
4: Minute pulse, positive flank
5: Minute pulse, negative flank
Function
Accuracy
Time tagging resolution
1 ms
Time tagging error with synchronisation once/60 s
±
1.5 ms
Time tagging error without synchronisation
±
3 ms/min