Setting group selector (GRP)
Chapter 10
Verifying settings by secondary
injection
16
Setting group selector (GRP)
Procedure
1.
Check the configuration of binary inputs that control the se-
lection of active setting group.
2.
Browse the ‘ActiveGroup’ menu to achieve information about
the active setting group.
The ActiveGroup menu is located in the local HMI under:
ServiceReport/ActiveGroup
3.
Connect the appropriate dc voltage to the corresponding bi-
nary input of the terminal and observe the information pre-
sented on the HMI display.
The displayed information must always correspond to the activat-
ed input.
4.
Check that corresponding output indicates the active group.
5.
Continue to test another function or complete the test by set-
ting the test mode to off.