Self-powered feeder protection
1MDB07217-YN
REJ603
Product version: 3.0
Issued: 2017-011-21
Revision: E
14
ABB
Table 24.
Very high-set phase overcurrent protection, stage I>>> / 50-2
Parameter
Value (Range)
Setting range of pick-up current ‘I >>>’
0.2...32.0 x In in steps 0.001, infinite for CT variant
Operation accuracy
1)
± 3.0% x In for value < 1.2 In , ± 3.0% x I for value ≥ 1.2 In
Operation mode
Definite time, Instantaneous
Operate time delay (DMT) ‘t >>>’
0.04...64 s in steps of 0.01
Operation time accuracy
1)
± 2.0% of set value or ± 30 ms
Reset ratio
0.98
1)
Operation time accuracy for protection functions when relay is in energised condition.
Table 25.
Low-set earth-fault protection, stage I0> / 51N
Parameter
Value (Range)
Setting range of pick-up current ‘I0 >’
External earth measurement (through CBCT or residual connection) :
0.01...2.0 x In in steps 0.01, infinite
Internal earth measurement : 0.1...2.0 x In in steps 0.01, infinite
Operation accuracy
1)
External earth measurement : ± 3.0% x In for value < 1.2 In ,
± 3.0% x I for value ≥ 1.2 In
Internal earth measurement : ± 9.0% x In for value < 1.2 In ,
± 9.0% x I for value ≥ 1.2 In
Operate time delay (DMT) ‘t0 >’
0.04...64 s in steps of 0.01
Operation time accuracy
1)
External earth measurement : ± 2.0% of set value or ± 30 ms
Internal earth measurement : ± 10.0% of set value or ± 30 ms
Operating curve type
IEC 60255-151:
Normal inverse, Very inverse, Extremely inverse, Long-time inverse
ANSI C37.112:
Moderate inverse, Normal Inverse, Very inverse, Extremely inverse
Special curves:
RI inverse, HR fuse, FR fuse
Time multiplier setting ‘k0’
0.02...1.6, in steps of 0.01
Operation time accuracy
1)
IEC, ANSI, HR, FR characteristics
RI characteristics
IEC, ANSI, HR, FR characteristics
RI characteristics
External earth measurement : class E(5) or ± 30 ms
External earth measurement : class E(7.5) or ± 30 ms
Internal earth measurement : ± 5.0% of set value or ± 30 ms
Internal earth measurement : ± 10.0% of set value or ± 30 ms
Reset ratio
IDMT : 0.96 and DT : 0.98
1)
Operation time accuracy for protection functions when relay is in energised condition.