11.1.6
Monitored data
Table 202:
SDDRFUF Monitored data
Name
Type
Values (Range)
Unit
Description
3I0
REAL
-
A
Magnitude of zero
sequence current
3I2
REAL
-
A
Magnitude of negative
sequence current
3U0
REAL
-
kV
Magnitude of zero
sequence voltage
3U2
REAL
-
kV
Magnitude of negative
sequence voltage
11.1.7
Operation principle
11.1.7.1
Zero and negative sequence detection
The zero and negative sequence function continuously measures the currents and
voltages in all three phases and calculates: (see figure
•
the zero-sequence voltage 3U
0
•
the zero-sequence current 3I
0
•
the negative sequence current 3I
2
•
the negative sequence voltage 3U
2
The measured signals are compared with their respective set values
3U0<
and
3I0>
,
3U2<
and
3I2>.
The function enable the internal signal FuseFailDetZeroSeq if the measured zero-
sequence voltage is higher than the set value
3U0>
and the measured zero-sequence
current is below the set value
3I0<
.
The function enable the internal signal FuseFailDetNegSeq if the measured negative
sequence voltage is higher than the set value
3U2>
and the measured negative
sequence current is below the set value
3I2<
.
A drop off delay of 100 ms for the measured zero-sequence and negative sequence
current will prevent a false fuse failure detection at un-equal breaker opening at the
two line ends.
Section 11
1MRK 502 048-UEN A
Secondary system supervision
310
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...