background image

ABB

5

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

coil is not current, but a voltage. Due to absence 
of ferromagnetic core, the sensor is linear up to the 
highest currents. 

The wide measurement range of sensors with high 
accuracy eliminates the need for high variants of 
conventional instrument transformers, resulting in 
simplified engineering, logistics and reduced inven-
tory. The low level voltage signals and integrated 
secondary cables contribute to easy and fast instal-
lation with enhanced safety.

6. Control

 

The relay offers control of one circuit breaker with 
dedicated push-buttons and guidance on local HMI 
for opening and closing. It includes two dedicated 
outputs for breaker control. The breaker control is 
also possible through optional MODBUS communi-
cation.

7. Measurement

 

The relay continuously measures phase currents 
and earth current. Earth current can be measured 
using external core balance current transformer or 
can be calculated internally. 

During service, the default view of display shows 
the most loaded phase current in primary terms 
(Amps) and the earth current in terms of nominal 
value of CT. The values measured can be accessed 
locally via the user interface on the relay or remotely 
via the communication interface of the relay. 

To maintain the measurement accuracy of the 
overall protection system, the sensor calibration 
constants available on the rating plate of sensors 
can be programmed to the relay. 

8. Event log

 

To collect sequence-of-events (SoE) information, 
the relay incorporates a non-volatile memory with a 
capacity of storing 100 events with associated time 
stamps with resolution of 1 milli second. Event log 
includes trip circuit supervision status, protection 

operation status, binary I/O status and relay fault 
code. The event logs are stored sequentially, the 
most recent being first and so on. The non-volatile 
memory retains its data also in case the relay tem-
porarily loses its auxiliary supply. 

The event log facilitates detailed post-fault analysis 
of feeder faults and disturbances. The SoE informa-
tion can be accessed locally via the user interface 
on the relay front panel or remotely via the commu-
nication interface of the relay. 

9. Recorded data 

The relay stores fault records of analog values for 
two trip events in non-volatile memory. The fault 
recording is triggered by the trip signal of protection 
function. A sample of analog value is recorded for 
every power frequency cycle. Fifteen such samples 
are recorded, five before the trip and ten after the 
trip event. These records enable the user to analyze 
the two most recent power system events. Each 
record includes the current values for three phases 
and earth current. 

The relay records the number of phase and earth 
fault trip events into dedicated trip counters. These 
trip counters can not be reset by the user and are 
stored in non-volatile memory. 

The recorded information can be accessed locally 
via user interface on the relay front panel and can 
be uploaded for subsequent fault analysis. 

10. Self-supervision and test function                                            

 

The relay’s built-in self-supervision system con-
tinuously monitors the state of the relay hardware 
and the operation of the relay software. Any fault 
or malfunction detected will be used for alerting 
the operator. A permanent relay fault will block the 
protection functions of the relay to prevent incorrect 
relay operation. 

The relay supports a built-in test mode which ena-
bles user to test the relay HMI and trip outputs. 

Summary of Contents for REF601

Page 1: ...Relion 605 series Relion 605 series Feeder protection and control REF601 Product Guide Relion 605 series...

Page 2: ...ions 13 18 Dimension and mounting 16 19 Selection and ordering data 17 20 Accessories and ordering data 18 21 Terminal diagram 19 22 References 20 23 Document revision history 20 Disclaimer The inform...

Page 3: ...ation specific parameters needs to set within the relay s intended area of application The settings can be changed by LHMI local human machin interface or through optional communication interface MODB...

Page 4: ...distribution substations The relay can be applied for the short circuit over current and earth fault protection of overhead lines and cable feeders of distribution and sub distribution network The re...

Page 5: ...lli second Event log includes trip circuit supervision status protection operation status binary I O status and relay fault code The event logs are stored sequentially the most recent being first and...

Page 6: ...d to core balanced current transformer split core cur rent transformer Relay binary input output overview Two binary inputs one for remote trip and one for remote reset One normally open trip output w...

Page 7: ...inuously 4 A For 1 sec 100 A Dynamic current withstand Half wave value 250 A Input impedance 100 m Rogowski coil sensor 250A 0 18V at 60Hz Linear current measurement 4A 25 kA Input type Current transf...

Page 8: ...me 5 A 3 A 1 A constant L R 40 ms at 48 110 220 V DC Current drain 2 20 mA Power consumption input 0 5 W two contacts connected in series Minimum contact load 100 mA at 24 V AC DC Trip circuit supervi...

Page 9: ...st value Reference Dry heat test humidity 50 96 h at 70 C IEC 60068 2 2 96 h at 85 C Dry cold test IEC 60068 2 1 Damp heat test cyclic 2 cycles at 25 C 55 C IEC 60068 2 30 humidity 93 Damp heat test s...

Page 10: ...o magnetic IEC 60255 22 3 class III 10 V m field immunity test Fast transient disturbance tests IEC 60255 22 4 class A 4 kV 5 0 kHz All ports Surge immunity test IEC 60255 22 5 IEC 61000 4 5 1 0 kV 1...

Page 11: ...0 M at 500 V DC Isolation resistance Table 15 Mechanical tests Description Type test value Reference Vibration tests IEC 60255 21 1 class II 10 150 Hz 0 035 mm 1 0 g Response 1 sweep axis Endurance Wi...

Page 12: ...tive 2006 95 IEC Standard EN 60255 27 2005 EN 60255 1 2009 Description Type test value Table 17 EMC compliance EMC directive 2004 108 IEC Standard EN 50263 2000 EN 60255 26 2007 Description Table 18 R...

Page 13: ...of 0 1 Operation time accuracy class E 5 or 30 msec 5 0 of set value or 30 msec IEC characteristics RI characteristics Reset ratio IDMT 0 96 and DT 0 98 Table 21 High set phase overcurrent protection...

Page 14: ...istics RI characteristics Reset ratio IDMT 0 96 and DT 0 98 Table 24 High set earth fault protection stage Io 50N Parameter Value Range Setting range of pick up current Io 0 5 4 0 x In in steps 0 25 i...

Page 15: ...ABB 15 1MDB07207 YN Feeder Protection REF601 Product version 2 0 Table 25 Transformer inrush detector Parameter Value Range Inrush threshold value 0 2 20 x In Ratio Setting 30 50...

Page 16: ...hout using an additional mounting accessories the REF601 can be easily flush mount ed on the panel The panel cut out for flush mouting Height 151 5 1 mm Width 121 5 1 mm Thickness of panel 2 0 3 0 mm...

Page 17: ...nformation in Fig 4 to gen erate the order number when ordering complete protection relays Figure 4 Ordering key for complete relay Example code REF601 B A 4 2 6 B A 1 X E Your ordering code Digit 1 2...

Page 18: ...tible sensors Item Order number KEVCR for integrated circuit breakers type VD4 HD4 KEVCR24OC2R0101 630A KEVCR24AC2R0102 1250A KECA for other applications where relay is panel mounted KECA 250 B1 1VL54...

Page 19: ...REF601 XK5 XK6 XK7 IL1 DIFF IL2 DIFF IL3 DIFF XK8 1 2 Io 1A XK4 1 2 BI Remote Trip 3 4 BI Remote Reset Uaux 1 2 XK9 3 4 XK10 1 2 Trip1 XK2 1 2 E F Trip 3 4 5 6 O C Trip Unit Ready 7 8 Bkr Close 9 10...

Page 20: ...revision history documentation such as technical reference manual installation manual operator manual and so on The selection tool on the Web page helps you find the documents by the document categor...

Page 21: ......

Page 22: ...ntact us 1MDB07207 YN E Copyright 2012 ABB All rights reserved ABB Ltd Distribution Automation Maneja Works Vadodara 390013 India Phone 91 265 2604386 Fax 91 265 2638922 www abb com substationautomati...

Reviews: